back-arrowclipboard-checkclipboardclose-2close-3close-4closeconstruction-2constructioncubecubescurva-fotometrica-oldcurva-fotometricadeletedesign-tooldesigndot-circledown-arrow-thindown-arrowdownload-2download-3downloaddrawingemailexpandfilefilterfountaingroupico-alimentazioneico-cavoico-coloriico-coperturaico-corpo-acciaioico-corpo-vetroico-dimensioniico-dinico-dmx-512ico-dmxico-isolamentoico-ondeico-pilaico-potenzaico-protezioneico-rbgwico-rdmico-sequenzeico-smartphone-controlico-sostituzioneico-zoneleft-arrow-thinleft-arrowlinklistlocation-thinlocationlogo-teclumenlogo-teclumen_oldmarker-fillmarkernext-arrowpayoffper-aquamright-arrow-thinright-arrowsearchsharesocial-facebooksocial-instagramsocial-linkedinsocial-pinterestsocial-twittersocial-whatsappsocial-youtubeteamwork-2teamworkteclumen-mobileteclumen-payoffteclumen-payoff_wteclumentimesuserwaterwaves

Zone 0 and Zone 1
ACADEMY

Zone 0 and Zone 1

In order to ensure the safety of bathers and those around the pool, areas are defined in pools where only SELV (Safety Extra Low-Voltage) can be used.
This voltage cannot exceed 12 V AC (alternate current) or 30 V DC (direct current).
In zones 0 and 1, only protection by SELV circuits with the safety source installed outside zones 0 and 1, or installed in zone 2 if its power supply circuit is protected by a differential protection device with a nominal differential current not exceeding 30 mA, is allowed.
Junctions are not allowed in zones 0 and 1. Junction boxes are only allowed in zone 1 if the circuits are SELV.
The reference standard is CEI 64-8. For further information, consult the link.